FireDOC Search

Author
Evans, D. D.
Title
Sprinkler Fire Suppression Algorithm for HAZARD.
Coporate
National Institute of Standards and Technology, Gaithersburg, MD
Report
NISTIR 5254, August 1993, 21 p.
Distribution
AVAILABLE FROM National Technical Information Service (NTIS), Technology Administration, U.S. Department of Commerce, Springfield, VA 22161. Telephone: 1-800-553-6847 or 703-605-6000; Fax: 703-605-6900. Website: http://www.ntis.gov
Book or Conf
U.S./Japan Government Cooperative Program on Natural Resources (UJNR). Fire Research and Safety. 12th Joint Panel Meeting. October 27-November 2, 1992, Building Research Inst., Ibaraki, Japan Fire Research Inst., Tokyo, Japan, Tsukuba, Japan, 114-120 p., ['1992', '1993']
Keywords
sprinklers | fire suppression | hazard analysis | cribs | crib fires | fire protection | algorithms
Abstract
Measurements of the heat release rate of a fully involved square base wood crib both before and during fire suppression with water spray from commercial sprinklers were used to develop a correlation for the exponential decay time constant of the fire heat release rate from the value at sprinkler actuation. This correlation is the basis for prediction of limits for heat release rates of furnishings during fire suppression. For 0.61 m square base wood cribs that are 0.61 m in height, the time constant varies with spray density. Using this result, the time constant for suppression at a sprinkler spray density of 0.07 mm/s is 410 s.