Capacity and Overload Tests of a 7 1/2 Ton Package Unit Air Conditioner. Final Report.
Coporate
National Bureau of Standards, Gaithersburg, MD
Sponsor
David Taylor Research Center, Annapolis, MD
Report
NBSIR 88-3723, January 1988, 26 p.
Distribution
Available from National Technical Information Service
Keywords
air conditioner | air conditioner testing | capacity testing | overload testing
Abstract
The National Bureau of Standards performed capacity and overload tests of a 7 1/2 ton package unit air conditioner for the David Taylor Research Center. The unit capacity was measured to be 83,200 Btu/hr (6.9 tons), the Energy Efficiency Ratio (EER) to be 8.58 Btu/Whr and the cooling effect ratio to be 62.7% at the requested capacity test condition. The unit failed to operate at the requested overload capacity test condition. Several additional tests were performed to more completely describe the performance of the unit.