FireDOC Search

Author
Abrams, M. S. | Gustaferro, A. H.
Title
Fire Tests of Poke-Thru Assemblies.
Coporate
Portland Cement Assoc., Skokie, IL
Report
Research and Development Bulletin
1971
22 p.
Keywords
concrete slabs | fire resistance tests | floors
Identifiers
electrical fittings; poke-thru fittings
Abstract
Unprotected poke-thru fittings can reduce the fire endurance of a floor significantly by providing openings or direct heat paths through the floor. This paper describes a series of fire testsof concrete slabs in which poke-thru fittings were mounted. Various types of protection were provided for the fittings, including sprayed insulation and heat shields. In some tests, modified fittings with built-in fire resistance were used. A total of 120 poke-thru assemblies were firetested - 100 3.3-ft slabs and 20 in full scale floor slabs. Fire endurance ranged from a few minutes to more than 4 hours, depending on the type and amount of protection. Data are presented in a manner to assist designers and fitting manufacturers in selecting protection methods to provide the required fire endurance.