FireDOC Search

Author
Mulroy, W. J. | Didion, D. A.
Title
Laboratory Investigation of Refrigerant Migration in a Split Unit Air Conditioner.
Coporate
National Bureau of Standards, Washington, DC
Sponsor
Department of Energy, Washington, DC
Report
NBSIR 83-2756
August 1983
Distribution
Available from National Technical Information Service
Keywords
air conditioners; refrigerants; heat pumps; pneumatic valves; regression analysis; evaporators; heat transfer; losses
Abstract
The relationship between cyclic refrigerant migration and cyclic loss for a residential, split-system air conditioner has been investigated. The cyclic refrigerant migration was measured at different points in the operating cycle by simultaneously shutting five pneumatic valves which isolated the refrigerant in the major system components. The refrigerant was then removed, weighed, and returned to the system. The unit tested was found to have a high initial capacity as migrated refrigerant was removed from the evaporator and then a low, slowly increasing capacity as trapped refrigerant was returned to the system from the accumulator. The unit performance was also compared to single and double time constant regressive approximations and to the time constant calculated from the evaporator mass and heat transfer coefficient. Although relationships between migrated refrigerant and cyclic capacity were observed, no practical refrigerant migration test method that would be less burdensome than the cyclic tests of ASHRAE Std. 116 appears possible at this time.