- Author
-
Davis, W. D.
|
Notarianni, K. A.
- Title
- Algorithm for Calculating the Plume Center Line Temperature and Ceiling Jet Temperature in the Presence of a Hot Upper Layer.
- Coporate
- National Institute of Standards and Technology, Gaithersburg, MD
- Book or Conf
- Fire Research and Engineering, Second (2nd) International Conference. (ICFRE2). Proceedings. ABSTRACTS ONLY. National Institute of Standards and Technology and Society of Fire Protection Engineers. August 10-15, 1997,
Gaithersburg, MD,
Slaughter, K. C., Editors,
113-113 p.,
1997
- Keywords
-
fire research
|
fire protection engineering
|
temperature
|
ceiling jets
|
pool fires
|
zone models
|
fire plumes
|
ceiling jets
|
sprinkler activation
- Abstract
- [ABSTRACT ONLY] The analysis of recent experiments (NIST TN 1423) using JP-5 and JP-8 pool fires performed in 15 m and 22 m high hangars suggest that plume center line temperature correlations found in the computer fire model FPETool (NISTIR 5486-1) under predict the ceiling temperature for large fires. The analysis was based on the results of thirty-three fire tests which had heat release rates ranging from 100 kW to 33 MW and ambient temperatures ranging from 8 deg C to 31 deg C. The ceiling jet correlation also requries modification since a comparison of predicted sprinkler activation using FPETool to measured sprinkler activation met with only limited success. The purpose of this paper is to present a new plume algorithm for the predicted sprinkler activation using FPETool to measured spirnkler activation met with only limited success.