- Twilt, L. | vandeWeijgert, J. C. A. | vandeHaar, P. W.
- Title
- Fire Endurance of a Horizontal GRP-Pipe With Insulated Steel Valve.
- Coporate
- Instituut TNO voor Bouwmaterialen en Bouwconstructies, Delft, The Netherlands
- Sponsor
- Stichting Coordinatie Maritiem Onderzoek, Rotterdam, Netherlands
- Report
- TNO-IBBC-B-91-0457, 1991, 28 p.
- Distribution
- AVAILABLE FROM National Technical Information Service (NTIS), Technology Administration, U.S. Department of Commerce, Springfield, VA 22161. Telephone: 1-800-553-6847 or 703-605-6000; Fax: 703-605-6900; Rush Service (Telephone Orders Only) 800-553-6847; Website: http://www.ntis.gov
- Keywords
- plastics pipes | fire endurance | shipboard fires | reinforced plastics | fire tests | ships | thermal insulation | valves
- Identifiers
- fiberglass reinforced plastics; pipes (tubes)
- Abstract
- The aim of the present investigation was to study the effect of a steel valve, mounted in a GRP-pipe system, on the fire endurance of the system. According to the current views within IMO, premature failure of the valve or leakage through the bolted flange connection between valve and GRP-flange can be accepted only if the GRP-pipe sections including the GRP-flanges connected to the valve are not damaged to such an extent that replacement is necessary.