Klote, J. H.
Title
Analysis of the Influence of Piston Effect on Elevator Smoke Control.
Coporate
National Bureau of Standards, Gaithersburg, MD
Report
NIST SP 983; NBSIR 88-3751, April 1988, 24 p.
Distribution
AVAILABLE FROM National Technical Information Service (NTIS), Technology Administration, U.S. Department of Commerce, Springfield, VA 22161. Telephone: 1-800-553-6847 or 703-605-6000; Fax: 703-605-6900. Website: http://www.ntis.gov TO VIEW NIST SP 983 GO TO Website: http://wtc.nist.gov/pubs/elevators
Book or Conf
Collected Publications Related to the Use of Elevators During Fires. NIST SP 983. May 2002, Bukowski, R. W.; Burgess, S. R.; Reneke, P. A., Editors, ['2002', '1988']
Keywords
smoke control | elevators (lifts) | hazard analysis | piston effect | pressurization | smoke
Abstract
This paper is part of a joint project between the United States and Canada to evaluate the feasibility of using elevators for the evacuation of the handicapped during a fire. The transient pressures produced when an elevator car move in a shaft are a potential problem for elevator smoke control. Such piston effect can pull smoke into a normally pressurized elevator lobby. This paper presents an analysis of an elevator smoke control system emphasizing the influence of piston effect on system performance. For most elevators the problem can be overcome by designs that prevent smoke from being pulled into lobbies, and equations for the amount of pressurization air to accomplish this are developed for two arrangements of supply air outlets. Where this approach is not feasible, the methods of analysis presented in this paper can be used to determine smoke infiltration for a hazard analysis.