FireDOC Search

Author
Breen, D. E. | Goodfellow, D. G.
Title
New Criteria for Fire Protection of Large Air Force Warehouses. Volume 2. Friction Loss in Pipes: Minimization by the Use of Chemical Additives. Technical Report.
Coporate
Factory Mutual Research Corp., Norwood, MA
Sponsor
Air Force Systems Command, Kirtland AFB, NM
Report
AFWL-TR-70-1; Volume 2
August 1970
24 p.
Keywords
warehouses | fire protection | fire suppression | fire fighting | fire detection | fire research | sprinkler systems
Identifiers
water additive systems; Air Force Warehouse (fuels and hazards)
Abstract
Water additive solutions were tested for relative effectiveness in reducing friction loss in turbulent flow. Polyox FRA and Separan AP 273 were judged superior in performance in a comparison of five candidate additives. A maximum increase of 2.5 in flow rate factor was attained in a simple gravity fed system. A subsequent test of Polyox FRA in a simulated sprinkler system showed no significant change in flow. This failure is believed to be due to faulty mixing. Methods to overcome this experimental difficulty are recommended.