FireDOC Search

Author
Ruffino, P. | diMarzo, M.
Title
Effect of Evaporative Cooling on the Activation Time of Fire Sprinklers.
Coporate
Maryland Univ., College Park
Sponsor
National Institute of Standards and Technology, Gaithersburg, MD
Book or Conf
Fire Safety Science. Proceedings. Seventh (7th) International Symposium. International Association for Fire Safety Science (IAFSS). June 16-21, 2003, Intl. Assoc. for Fire Safety Science, Boston, MA, Worcester, MA, Evans, D. D., Editors, 481-492 p., 2003
Keywords
fire research | sprinklers | evaporation | cooling | activation time | sprinkler activation | equations
Identifiers
sprinkler skipping; evaporative cooling; Response Time Index (RTI); conditions for the sprinkler tests; sprinkler activation times in [s]: model predictions and experiments
Abstract
Arrays of fire sprinklers are installed in buildings to protect the property and their occupants against the damages of fire. When a fire occurs, the sprinkler closest to the fire location typically activates first and releases water droplets into the rising plume of hot gases. Part of these droplets is entrained by the plume and may impact on adjacent sprinklers providing evaporative cooling and thus delaying their activation. The current model that simulates the thermal response of fire sprinklers does not include this evaporative cooling effect; therefore, a new model is proposed to extend the applicability of the previous formulation. The new model includes one parameter, determined experimentally, that is associated to the evaporative cooling effect. Commercially available sprinklers are tested to assess the accuracy of the proposed model for a range of conditions (hot gas temperature and velocity, water volumetric fraction and sprinkler orientation with respect to the flow).