FireDOC Search

Author
Peterson, H. B. | Jablonski, E. J. | Burns, R. E. | Gipe, R. L. | Whitehurst, C. L.
Title
Evaluation of a Redesigned FP-180 Water Motor Proportioner for AFFF. Interim Report.
Coporate
Naval Research Laboratory, Washington, DC Hughes Associates Inc., Kensington, MD
Report
NRL Memorandum 5339, June 18, 1984, 24 p.
Distribution
Available from National Technical Information Service
Keywords
fire fighting | fire extinguishing agents
Abstract
The objective of the project was to redesign the FP-180 to proportion AFFF, to improve reliability and to extend the usable life of the pump. Specific tasks were: (1) redesign the gear ratio from 1 to 1 to a higher rtio to provide AFFF concentration of 5% to 15% over the range of 60 gpm to 180 gpm; (2) limit the pressure drop across the water motor to 23 psi at 60 gpm and 33 psi at 180 gpm with a 150 psi inlet pressure; (3) develop new shaft seals and new bearings that will effectively reduce leakage and freezing problems.