Thomas, I. R.
Title
Fires in Enclosures With Single Ventilation Openings: Comparison of Long and Wide Enclosures. BFRL Fire Research Seminar. VHS Video.
Coporate
Victoria University of Technology, Melbourne, Australia
Report
Video
July 13, 1999
Keywords
enclosures | ventilation
Abstract
The rate of burning of fires in enclosures is usually assumed to be proportional to the ventilation factor. This paper reports an experimental program designed to investigate the influence of opening width and enclosure shape on the burning rate by comparing the burning rate and behaviour of fires in long enclosures and wide enclosures with similar openings. Fire tests were conducted in enclosures 1500 mm by 600 mm by 300 mm high with ventilation openings of several widths. It was found that the burning behaviour and fuel mass loss rates of fires in long and wide enclosures differ markedly when the width of the ventilation opening is less than the full width of the enclosure. When the ventilation opening width is equal to that of the enclosure, the flows within the enclosure are essentially two dimensional, but when the opening width is less than that of the enclosure the flows within the enclosure are more complex and three dimensional. The mass loss rates for the same opening sizes in wide enclosures were found to be substantially greater than those in long enclosures for both full width (in the long enclosure) and partial width openings.