Specification for Clamp, Fire Hose Shutoff.
Coporate
Department of Agriculture, Washington, DC
Report
Interim Specification 5100-00245, April 1972, 7 p.
Keywords
fire hoses | specifications | water flow | forest fires | brush fires
Abstract
The purpose of the hose shutoff clamp is to temporarily shut off (squeeze off) the flow of water in fire hoses. These fire hoses are in nominal sizes of 1- and 1 1/2-inch, and are single-jacket rubber-lined as per Forest Service Specifications No. 182 and 5100-00186. The hoses are used by the USDA Forest Service primarily in fighting forest and brush fires. The clamp must be lightweight and compact enough to be carried without difficulty in a fireman's hip pocket or coveniently carried on a belt loop. It must be simple in construction for easy manual operation. The clamp must be able to shut off water in ahose at 300 psi.