Underwriters Laboratories, Incorporated
Title
Report on Wall and Partition Facings and Accessories for Use in a Nonbearing Wall. Walcon Corporation, Ecorse, Michigan.
Coporate
Underwriters Laboratories, Inc., Northbrook, IL
Report
File R4193-2
May 18, 1971
33 p.
Keywords
walls | partitions | fire tests | gypsum | wallboard
Abstract
This report describes the results of fire tests conducted on a nonbearing wall assembly constructed of four layers of 5/8-in. thick listed gypsum wallboard, faced on one side with steel liners and on the other side with aluminum facing units. The wall assembly was erected in the test frame opening as shown on Ills. 1 and 2. The object of this investigation was to establish a fire resistance classification for the wall assembly, erected and constructed of materials conforming in quality and physical properties to those described herein, by means of the fire endurance and hose stream tests conducted in accordance with the Standard, Fire Tests of Building construction and Materials, UL 263 (ASTM E 119, NFPA No. 251).