Title
Analysis of Data from the Energy Monitoring and Control System at the Norris Cotton Federal Office Building.
Coporate
National Bureau of Standards, Washington, DC
Sponsor
Department of Energy, Washington, DC
Report
NBSIR 81-2358, November 1981,
Distribution
Available from National Technical Information Service
Keywords
buildings; data processing; data; monitoring; control equipment; commercial buildings
Identifiers
energy conservation; energy use
Abstract
The Norris Cotton Federal Office Building (NCFOB) in Manchester, New Hampshire, is a medium-size office building, occupied in September 1976, designed to serve as a demonstration and a feasibility test for energy-conserving building features. A building energy monitoring and control system was operated as a data acquisition system over a 13-month period ending in September 1980. Experience encountered during the checkout and operation of the system is discussed. Results from data reduction procedures used to calculate approximately 160 parameters describing the energy performance of the building are presented on a monthly basis. Hourly data are also presented for daily building operation profiles, building envelope performance, and performance of the mechanical systems.