FireDOC Search

Author
Breden, L. H.
Title
Full-Scale Corridor Fire Experiment Using A Glass Fiber Carpet. Final Report.
Coporate
National Bureau of Standards, Gaithersburg, MD
Report
NBSIR 75-782, December 1975, 32 p.
Distribution
Available from National Technical Information Service
Keywords
carpets | corridor tests | fire tests | flammability | glass fibers | weight loss
Abstract
A corridor fire experiment was carried out using a glass fiber carpet. It was observed that with a fuel loading of 2.7 pounds per square foot of wood in an adjacent fire room, no propagation of the fire occurred down the corridor. The glass fiber carpet in the burn-room became discolored and there was a significant weight loss of the carpet directly in contact with the fire. The carpet did not produce significant levels of smoke and did not spread the fire into the corridor.