FireDOC Search

Author
Hermodsson, T. | Wickstrom, U.
Title
Modification of the Plate Thermometer: Proving Tests at SP and WFRC.
Coporate
Swedish National Testing and Research Institute, Boras, Sweden
Report
SP Report 1997:32, 1997, 33 p.
Keywords
thermometers | fiberboards | thermocouples | tests
Identifiers
fire resistance furnace; plate thermometer
Abstract
Different plate thermometer (PT) designs have been evaluated at the Swedish National Testing and Research Institute (SP) and at Warrington Fire Research Centre (WFRC) in England. The results obtained show that the ceramic fiber board in the original PT can be replaced with a non health hazardous calcium silicate fiber board and that the 1 mm thermcouple could be replaced with a 3 mm TC without changing the thermal characteristics. In addition one test indicated that the size of the plate could not be reduced without changing the temperature readings. The PT is used for controlling furnace temperature and harmonizing thermal exposure in fire resistance furnaces and is proposed for the new European standard EN 1363 Part 1.