FireDOC Search

Author
Rockett, J. A. | Keski-Rahkonen, O. | Heikkila, L.
Title
HDR Reactor Containment Fire Modeling With BRI2.
Coporate
Fire Analysis and Modeling, Washington, DC VTT-Technical Research Center of Finland, Espoo
Report
VTT Publications 113, September 1992, 88 p.
Keywords
nuclear reactors | fire tests | fire protection | fire safety | simulation | room fires | containment | wind velocity | plumes | vents | burning rate | geometry
Identifiers
test reactors; hatches; experimentation; HDR; BRI2
Abstract
Fire tests at the German test reactor, HDR, were simulated using a Japanese zone model code, BRI2. Eight and ten room models of the containment building were developed. Critical phenomena occurring during simulation were explored. BRI2 can be used for this type of work but care must be exercised where a side wind increases entrainment by the fire plume. Horizontal vents were described by effective vertical vents. Effect of location of the vent to ambient was found critical during severely oxygen limited burning.