FireDOC Search

Author
Levine, R. S.
Title
Full Scale Simulation of Sharon, Pennsylvania (PA) Fire: Data and Computer Analysis. CFR Video Seminar.
Coporate
National Institute of Standards and Technology, Gaithersburg, MD
Report
Video, July 18, 1989,
Keywords
predictive models | simulation | computer programs | carbon monoxide | carbon dioxide | fire investigations
Identifiers
SHARON 2; FAST 18 codes; HARVARD 6.3 codes
Abstract
The Sharon fire killed 3 persons, but considerable physical evidence remained. It apeared that very high CO occurred rapidly in an upstairs bedroom. The fire was successfully simulated in Bldg. 205 in a 7 room two story test, called SHARON2. The data are used to verify (or not) predictions from the FAST 18 and HARVARD 6.3 codes. Experimentally it was found that this large fire in a small structure lead to CO/CO2 ratios as high as 0.5, and that smoke detectors likely would not give adequate warning.