FireDOC Search

Author
Payne, W. V. | Domanski, P. A.
Title
Comparison of an R22 and an R410A Air Conditioner Operating at High Ambient Temperatures.
Coporate
National Institute of Standards and Technology, Gaithersburg, MD
Report
R2-1,
Book or Conf
International Refrigeration and Air Conditioning Conference. Proceedings. July 16-19, 2002, West Lafayette, IN, 2002
Keywords
high temperature | ambient temperature | tests | air conditioning | uncertainty
Identifiers
Coefficient of Performance (COP); measurement uncertainty at 95% confidence level; test conditions; R22 system tests; R410A system tests
Abstract
R22 and R410A split air-conditioning systems were tested and compared as outdoor temperature ranged form 27.8 ºC (82.0 ºF) to 54.4 ºF (130 ºF). The R410A system tests were extended t 68.3 ºC (155.0 ºF) ambient temperature with a customized compressor. Capacity and efficiency of both systems decreased linearly with increasing outdoor temperature, but the R410A system performance degraded more than the R22 system performance. Operation of the R410A system was stable during all tests, including those with the customized compressor extending up to the 68.3 ºF (155.0 ºF) outdoor temperature and resulting in a supercritical condition at the condenser inlet. No noticeable changes in noise level or operation on the system was noted.