Ingason, H.
Title
Fire Experiments in a Two Dimensional Rack Storage. BRANDFORSK Project 701-917.
Coporate
Swedish National Testing and Research Institute, Boras, Sweden
Report
SP REPORT 1993:56, 1993, 29 p.
Keywords
pallet storage | flame height | mass flow | flues | flow rate | experiments
Identifiers
rack storage; line burner
Abstract
Flame heights and air flows in a two dimensional rack storage were investigated. The width of the vertical flue is found to be the predominant geometrical parameter controlling the flue flow. The mass flow rate increases nearly linearly with the width. Variation of the horizontal flue heights was found to have negligible effects on the vertical flue flow. For a certain vertical flue width, the mass flow rate is found to be nearly constant independent of the heat output. Experimental results indicate a linear relationship between the flame height and the ratio of heat output to the vertical flue width. A ratio of entrained air to the stoichiometric air requirements at the flame tip is found to be 7.5. Experiments were carried out using inert boxes and a diffusion propane line burner located at the bottom of the rack. The rack was 0.59 m long and between 1.14 m and 1.34 m in height (4 boxes). The size of the rack is about 1/3 of what can be expected in a real rack storage.